Maintenance steps and discharge precautions of Guangdong yuasa battery

ith the increasing frequency of battery usage, accidents caused by YUASA battery failure have occurred continuously in recent years, which have affected and threatened the safe operation of equipment. Therefore, strengthening operation management, effectively reducing accidents, preventing communication interruption and other accidents, and regular inspection in daily maintenance is a vital work. We should not wait for accidents to start to pay attention to maintenance and inspection work. It's too late to mend our mistakes, and taking precautions is the right way of maintenance and management!

Daily maintenance steps of YUASA battery room

1. Keep the YUASA battery surface clean; check the connection condition of battery or YUASA battery rack regularly.

2. Establish daily operation records of YUASA battery and record relevant data in detail for future use.

3. Do not discard the used YUASA batteries at will. Please contact the Yuasa manufacturer for recycling.

4. During the storage of Yuasa battery, the battery shall be recharged regularly according to the requirements in the document.

If you need to manage the YUASA battery discharge, you should pay attention to the following points

A. Do not use any organic solvent to clean the YUASA battery;

B. Never open or disassemble the safety valve, otherwise, the performance of the YUASA battery will be affected;

C. Be careful not to block the vent of the safety valve to avoid YUASA battery explosion;

D. It is recommended that the initial current should be set within o.125c10a when equalizing charge / make-up power;

E. It is better to use the battery in the temperature range of 20 ℃ ~ 30 ℃ to avoid overcharging;

F. Make sure to control the voltage of Yuasa battery within the recommended range to avoid unnecessary loss;

G. If the battery needs to be discharged frequently due to poor power consumption conditions, it is recommended to set the recharging current at o.15-o.18c10a;

H. The battery can be placed vertically or horizontally, but it can never be used upside down;

1. It is forbidden to use the battery in a closed container;

J. When using and maintaining the YUASA battery, please use insulating tools. Metal tools cannot be placed on the YUASA battery;

CONTACT US